WEKO3
インデックスリンク
アイテム
衝撃電庄による埋設地線のインピーダンス特性
https://fukuyama-u.repo.nii.ac.jp/records/7593
https://fukuyama-u.repo.nii.ac.jp/records/75934bf641ef-00af-4595-ace6-a3628bd87143
名前 / ファイル | ライセンス | アクション |
---|---|---|
![]() |
|
Item type | 紀要論文(ELS) / Departmental Bulletin Paper(1) | |||||
---|---|---|---|---|---|---|
公開日 | 1979-01-01 | |||||
タイトル | ||||||
タイトル | 衝撃電庄による埋設地線のインピーダンス特性 | |||||
タイトル | ||||||
タイトル | Input Impedance Characteristics of Counterpoises for an Impulse Voltage Wave | |||||
言語 | en | |||||
言語 | ||||||
言語 | jpn | |||||
資源タイプ | ||||||
資源タイプ識別子 | http://purl.org/coar/resource_type/c_6501 | |||||
資源タイプ | departmental bulletin paper | |||||
ページ属性 | ||||||
内容記述タイプ | Other | |||||
内容記述 | P(論文) | |||||
記事種別(日) | ||||||
値 | 論文 | |||||
著者名(日) |
中沢, 力
× 中沢, 力 |
|||||
著者名よみ | ||||||
識別子Scheme | WEKO | |||||
識別子 | 41252 | |||||
姓名 | ナカザワ, ツトム | |||||
著者名(英) | ||||||
識別子Scheme | WEKO | |||||
識別子 | 41253 | |||||
姓名 | Nakazawa, Tsutomu | |||||
言語 | en | |||||
著者所属(日) | ||||||
値 | 福山大学工学部電子電気工学科 | |||||
抄録(英) | ||||||
内容記述タイプ | Other | |||||
内容記述 | Counterpoises act as a sort of electric grounding equipments in power transmission line systems. They are horizontal wires buried in the earth at a depth of about a half meter, and tied to the tower base. Regarding the counterpoise as an electric circuit of one conductor with distributed line constants, we analyze the input impedance of the counterpoise for an applied impulse voltage by the basic theory of distributed constant circuit. The variation of the input impedance with time is as follows: It starts with the initial surge impedance, and subsides exponentially to the final leakage resistance of the counterpoise. The impedance characteristics of the counterpoise may be classified into (1) the inductive, (2) the capacitive, and (3) the resistive types depending on the effects of the resistivity of the soil, the length of the counterpoises and the number of the parallel counterpoise wires. The results of the analysis are confirmed by comparison with those of a series of field tests carried out by Research Laboratory of Shikoku Electric Company. It will be worthy of notice that the assembly of several short counterpoise wires acts as the capacitive circuit under special conditions. | |||||
雑誌書誌ID | ||||||
収録物識別子タイプ | NCID | |||||
収録物識別子 | AN00217655 | |||||
書誌情報 |
福山大学工学部紀要 巻 1, p. 18-25, 発行日 1979 |